        • XJ seriesCarry type short-circuit grounding wires

           

          The instruction for use

           

           

          Shanghai SuTe electric Co., LTD

          XJ series portable short earthing
          I. Overview
          1, XJ series portable short-circuit ground wire is the company recently developed a new generation of products. Products meet all the performance indicators are presented SD332-89 "portable short-circuit ground wire technology standards" requirements. Products in the August 10, 2001 security tools by the power and Testing Center of the type testing. Pilot projects are all qualified.
          2, XJ series portable short-circuit ground wire from the insulated operating rod, wire clips, short routes, grounding wire, grounding Swiss sub, bus clip, earth clamp and other components, wire holder, earth clamp are made of high quality aluminum alloy die-casting, high strength, and then by the clamp surface surface treatment should not be oxygen. Operating rod with epoxy resin imported refined into color management, good insulation properties, high strength, light weight, bright, smooth appearance, processing skills, is a technology leader in the manufacture of similar products.
          3, XJ series portable short-circuit ground wire can be divided into sub-phase grounding, combined-phase ground. Use of different voltage, a single, multi-section rod-type operation. Transformer short-circuit grounding wires are used (level folder), lines (round clip).
          Second, technical indicators
          1, the use of environmental conditions:
          (1) Ambient temperature: -25 ℃ ~ 55 ℃
          (2) Relative temperature: ≤ 90%
          (3) Use: indoor and outdoor weather, no rain
          2, the ground operation rod size (Table I)

          All sorts of different voltage grade device name Insulation parts length (mm Handshake section length (mm) Total length (mm)
          Consumers10KV below electrical equipments According to the work place does not make the rules
          Consumers 10KV equipment and transmission line 700 300 100
          35KV equipment and transmission line 900 600 1500
          63KV equipment and transmission line 1000 600 1600
          110 KV equipment and transmission line 1300 700 2000
          220 KV equipment and transmission line 2100 900 3000
          330 KV equipment and transmission line 3000 1100 4100
          500 KV equipment and transmission line 4100 1400 5500
          220-500 KV transmission line insulation overhead ground 700 300 1000
          Laboratory and testing equipment grounded 700 300 1000
          3, grounding operation great mechanical strength (table 2)
          Static tension (N) Flexural strength
          1470 Grounding operation great working part weight twice
          4、Grounding operation great insulating properties (table 3)
          The rated operating voltage (KV) Consumers 10KV and below 35 63 110 220 330 500 220-500 Insulation overhead conductors Test equipment

          Preventive test voltage (KV) 44 93.5 167 219 438 567 758 44 44
          Factory test voltage (KV) 48 102 184 241 482 634 836 48 48
          Type test voltage (KV) 53 112 202 265 530 679 920 53 53
          Wet test voltage (KV) 40 90 159 210 400 600 — 40 40

          3, the XJ portable short-circuit grounding line selection, use and maintenance instructions
          1, according to the safety work instruction correct selection of short-circuit ground.strike suspension quantity, the correct choice suspension site, correctly use short-circuit grounding wires.
          2, carrying type short-circuit ground.strike choice shall withstand short-circuit current largest suspension of electricity, its rated short-circuit current value is not less than the largest suspension electrical fault current when not remove except reclose, still should consider secondary short-circuit current blunt short-circuit current impacts on short-circuit ground.strike short-circuit current rated influence.
          3, short-circuit grounding the length of the line should be suitable for the size of the equipment and fixed ground point distance, its rated short-circuit current squares rated time for product value is not less than the fault current squares fault time the product value. If the ground wire length less than junction distance of 1.2 times, can lead to more serious than type test when the stress too long makes short-circuit at work now too high and ground strongly swinging.
          4, according to convenient suspension short-circuit ground.strike requirement and the choice of wire clip model. Grounding operation great choice should be pensile point system and rated voltage is consistent, the suspension short-circuit ground.strike should guarantee the working staff, ground wire and charged equipment maintain necessary safety distance. In the end hanging completed the ground.strike before work of the staff should stay grounded conductor maintain certain safety distance.
          5, carrying type short-circuit ground.strike ago, electric power, confirm the experience on equipment without voltage after be conducted. First the grounding clip connection to the ground, and then operated online conductor bar respectively court since clip tightly. In equipment wires dismantling period route ground.strike sequence and appeal instead.
          6, erect short-circuit grounding wires, he and charged equipment distance considering the influence of ground wire to swing, the safe distance is not less than safe working procedures prescribed by the numerical.
          7, hanging point if no fixed place, can meet the available to temporary grounding electrodes as temporary ground point, grounding rods embedded depth of underground should not be less than 0.6 M.
          8, carrying type short-circuit grounding wire should be in air circulation, environmental dry special place deposited, before each use all should carefully check whether its are intact. Find wire clip craze, connection, become loose, security layer damaged. Soft copper bare, should be banned.
          9, shall be in compliance with the circuit safety work codes require regular inspection, (check project with ex-factory inspection)
          10, after the test qualified carry short-circuit withstand type grounding wires in general should be scrapped short-circuit after treatment.
          4, this company specialized designed, development, production, sales circuit safety tools.

           

          Shanghai SuTe electric Co., LTD
          ephone:

          Zip code: 200443
          Url: http://
          Address: Shanghai altogether kang road 1018 number

           

           

           

           

           

           

        主站蜘蛛池模板: 日韩人妻一区二区三区蜜桃视频| 精品黑人一区二区三区| 在线观看国产一区二区三区| 视频一区在线播放| 91无码人妻精品一区二区三区L| 国产一区二区三区在线看片| 国产一区二区成人| 无码精品人妻一区二区三区免费看 | 波多野结衣久久一区二区| 中文字幕一区二区在线播放| 色妞AV永久一区二区国产AV| 一区一区三区产品乱码| 亚洲国产成人久久综合一区77| 亚洲码欧美码一区二区三区 | 三上悠亚日韩精品一区在线| 无码少妇一区二区三区浪潮AV| 亚洲国产欧美日韩精品一区二区三区| 国产成人精品一区二三区在线观看| 3D动漫精品啪啪一区二区下载| 国产一区二区电影| 国产在线视频一区| 精品国产一区二区22| 日本精品夜色视频一区二区| 夜夜精品视频一区二区| 国产精品制服丝袜一区| 大香伊人久久精品一区二区| 亚洲av乱码一区二区三区 | 91精品一区二区综合在线| 美女一区二区三区| 亚洲一区中文字幕久久| 色狠狠一区二区三区香蕉| 人妻无码久久一区二区三区免费| 久久免费区一区二区三波多野| 中文字幕一区在线播放| 亚洲国产精品一区二区久久| 色窝窝无码一区二区三区成人网站 | 99久久精品国产高清一区二区| 亚洲熟妇av一区二区三区漫画| 亚洲av无码一区二区乱子伦as| 国产手机精品一区二区| 日本一区免费电影|